ExtractionTek’s modular ClDl Control Areas offer professional extraction facilities a scalable approach to compliant extraction in all legal Cannabis markets. These Modular designs offer a variety of sizes and heights to fit even the toughest of installation scenarios. Designed and manufactured in the U.S. we employ the highest-quality domestic materials and components in an easy to install, safe and efficient ClDl Control Room design.
Compliances
UL Listed to UL 1389 for C1D1 locations
NFPA 70
NFPA 58
NFPA 55
NFPA 1
NFPA 33 with appropriate duct work (not provided)
UL 508A
International Mechanical Code 510
International Fire Code Ch. 39
Proudly Engineered and Fabricated in Denver, Colorado, USA
Third Party Engineer Peer Reviewed
Utility Requirements
• Electrical connection via 230V 3p 60Hz
• Requires 50A connection
• Internal electric for equipment supplied via C1D1-rated motor disconnect and receptacle
• Uniquely designed plenum wall construction provides uniform airflow across the booth
Fire Rated Door
• 16-gauge galvanized door(s) with full body polystyrene core Include half window
• Meet or exceed ANSI 250-4 and ANSI 250-8 fire rating
• Double doors standard on booths SS-1404 and larger
Fan Control
• Adjustable up to 10,000 CFM (most stringent municipal codes)
• Base ventilation rate of 1500 CFM maintains net negative interior pressure (-0.02 w.c.) and provides greater than 50 air changes per hour
• Includes interior emergency purge push-button control